Thomas & Betts
Sales Partner Login
      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     
Load Sectionalizer Interrupters

Load Sectionalizer Interrupters
Click on photo for graphical representation

The Joslyn Load Sectionalizing Interrupter (LSI) converts isolating switches to provide interrupting capability for sectionalizing transmission loops, loop splitting and line charging current interruption. The LSI minimizes the possibility of a switching error as sequential switching of a loop system is eliminated, thereby improving personal safety and increasing system flexibility. The unique design automatically determines the required function and inserts the proper interrupter into the power circuit.

LSIs can be applied to disconnect switches rated 69kV through 161kV. They can be supplied, mounted, and preadjusted on Joslyn isolating switches to provide a complete interrupter switch. Conversion of an existing air switch is easily achieved since no special tools or training is required.


Maintenance-Free  
  Long life of 5,000 operations.
Ease of Installation
  Three phase sets can be installed quickly and easily in approximately 4 hours.
Rugged Construction
  Anodized aluminum mechanism housing protects against corrosive action and sealed vacuum interrupter chamber is sealed against moisture, ultraviolet activity, and contamination.
Proven Performance
  Installations of more than 35 years demonstrate the reliability and proven performance of the interrupter.
Air Switch Ratings Unaffected
  The continuous, momentary, and impulse ratings of the switch are unaffected since the LSI is in the power circuit for a few seconds.
    

Loop Switching/Parallel Switching
System Voltage
(kV)
Interrupting Current
(Amperes)
Maximum Peak
Recovery Voltage
(kV)
69-230
2000
30
                 
Line Dropping and Cable Switching Ratings
System Voltage
(kV)
Approximate Line Length
(Miles)
Current
( Amperes)
69
70
15*/20
115
50
20
138
30
15
161
20
10
* with Voltage Limiter Attachment
             
Transformer Magnetizing Switching Ratings
System Voltage
(kV)
Transformer Size
(MVA)
69 70
115 110
138 150
161 200
230 300
    
Ordering Information
1 Specify air switch manufacturer
2 Supply switch model number
3 Specify voltage and current rating
4 Indicate size of insulator bolt circle
5 Describe blade movement including rotation as viewed from hinge end
6 Specify application, system voltage and grounding
  

Joslyn Hi-Voltage Royce Thompson Fisher Pierce

Home | About Us | Products | Library | Contact Us | Chinese Site

Joslyn Hi-Voltage - 4000 E 116th Street, Cleveland, Ohio 44105 USA   Email: T&B Contact Information
Copyright © 2001 Joslyn Hi-Voltage. All rights reserved.
   
Royce Thompson