      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     
AutoCap Series 4400

AutoCap Series 4400

The Fisher Pierce AutoCap™ is a one-to-four season programmable controller. It can operate on the basis of VAr, voltage, current, temperature, time, and combinations of these inputs. It also includes complete load data and event recording from which reports can be created.

The AutoCap™ Series 4400 Adaptive Controller and Recorder adapts itself to the installation. The controller automatically corrects for installation errors such as sensing voltage and current from different phases, reversed current signal wiring, reversed Trip/Close wiring.


The AutoCap™ Series 4400 utilizes SmartSet application software which is Windows-based for easy programming.

Adaptive VAr Control
  Automatically measures the size of the bank, and establishes VAr setpoints for maximum energy loss reduction.
Adaptive Voltage Guard
  Identifies voltage change from bank switching and inhibits Close operation if Voltage Guard plus present line voltage exceeds high voltage limit.
PhaseFind Function
  Locates current signal phase with respect to voltage phase and compensates for phase rotation and reversed wiring.
Reverse Power Functions
  Calculates proper Var setpoints to compensate for altered Var measurement in this condition.
Reverse Trip/Close Detection
  Automatically senses reverse wiring of the Close and Trip drive circuits which inhibits all switching (except manual).
Anti-hunt Function
  Automatically compensates for rapid bank tripping due to cycling loads or interaction from other switched banks on the feeder.
Undervoltage Inhibit
  Protects the capacitor bank switch from damage caused by low voltage.
      

Easy Programming
  Windows-based software allows programming for up
to 4 seasons, each with primary & override functions.
Multi-Function
  In addition to basic functions, override functions,
voltage bias, and reverse power control modes, additional functions such as real-time monitoring,
user programmable calendars, switching time delays/inhibits, and neutral current lockouts are provided.
Extensive Data Recording
  Recording capability includes a full spectrum of
user-defined load data & controller operations and
are easily uploaded via RS-232 or optional optical port.



Report Generation Capability
  Load data reports provide a spread sheet format file, graphing of load data, direct edit graph time period, Trip/Close status, and report printing and includes many editing features.
     
    
Specifications
               
Ordering Information
Example
Model: 
44 1 1 N - C T S - SK 7 1 A
Section: 
1 2 3 4 - 5 6 7 - 8 9 10 11
Section 1 Basic Model Number
44 Autocap programmable capacitor controller in compact enclosure
Section 2 Line Current Input (Current sensing device ordered separately
1 Fisher Pierce 1301 line post sensor (60A/V) or Lindsey sensor (100A/V)
2 CT (5A secondary)
0 None
Section 3 Neutral Current Sensor
1 Fisher Pierce AT929 sensor with 6 foot lead (supplied)
2 CT (not supplied)
3 VT (not supplied)
0 None
Section 4 Optical Communication Port
F Supplied
N None
Section 5 Counter/Display
C Electro-mechanical counter only
D 2-line display only (read only)
E Electromechanical counter and 2-line display (read only)
P Panel Set "Programmable 2 Line Display"
K Panel Set with Mechanical Counter "Programmable 2 Line Display"
N None
Section 6 Temperature Sensor
T Supplied
N None
Section 7 Memory
S Standard 32K
E Expanded 128K
Section 8 External Wiring and Mounting Configuration
  Section 8 Four Jaw Meter Socket Mounting and Wiring
Section
8
1 2 3 4 5 6 External
ND Lug
Enclosure Current
Inputs
FJ L N/GND TR CL - - NO LEXAN NONE
GJ L N/COM TR CL - - YES LEXAN/ALUM NONE

Section 8 Six Jaw Meter Socket Mounting and Wiring
Section
8
1 2 3 4 5 6 External
GND Lug
Enclosure Current
Inputs
SJ CSL N/GND L TR CSH CL NO LEXAN LINE ONLY
TJ CSL N L TR CSH CL YES LEXAN/ALUM LINE ONLY
SM L N/GND CSL CSH TR CL NO LEXAN LINE ONLY
TM L N CSL CSH TR CL YES LEXAN/ALUM LINE ONLY
SL L N/GND NSL NSH TR CL NO LEXAN NEUTRAL ONLY
TL L N NSL NSH TR CL YES LEXAN/ALUM NEUTRAL ONLY
SK L N/GND/COM NSH CSH TR CL NO LEXAN LINE+NEUT
TK L N/COM NSH CSH TR CL YES LEXAN/ALUM LINE+NEUT

Section 8 Bracket Mounting with Terminal Strip
Section
8
  External
GND Lug
Enclosure Current Inputs
BJ: POLE
WJ: WALL
WIRE TO TERMINAL STRIP AS SHOW BELOW YES ALUM NONE, LINE, NEUTRAL OR LINE+NEUTRAL

Terminal Strip (Aluminum Enclosure Only)

Socket for CT shorting switch available for SJ & TJ wiring

GND=System ground
N = Neutral
L = Line
RLY = Output relay armatures
CL = Close
TR = Trip
CSH = Line current signal High
CSL = Line current signal Low
NSH = Neutral current signal High
NSL = Neutral current signal Low

View looking
into socket

* Broken lines between terminals indicate removable jumper
Section 9 Enclosure Type
7 Lexan (Meter socket mounting only)
8 Aluminum
Section 10 Voltage/Frequency

1

120 Vac, 60 Hz
2 240 Vac, 60 Hz
3 120 Vac, 50 Hz
4 220 Vac, 50 Hz
Section 11 Factory Code
  