      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     
AutoCap Series 4500

AutoCap Series 4500 The Fisher Pierce AutoCap Series 4500 Controller-Recorder combines the AutoCap Series 4400 Adaptive Capacitor Controller with data radios in the same enclosure for two-way communications. This integration eliminates the need for additional communication equipment. The result is a powerful tool for discrete feeder management, data gathering, trouble shooting, system evaluation and analysis.

The Series 4500 AutoCap™ is a one-to-four season programmable controller.


It can operate on the basis of VAr, voltage, current, temperature, time, and combinations of these inputs. It also includes complete load data and event recording from which reports can be created.

The Series 4500 AutoCap™ utilizes SmartSet application software (Windows based) which allows the user to program the controller, monitor real-time line conditions, retrieve and graph load survey data from any PC/modem. The controller can be configured to operate under SCADA control or as a local control with SCADA override.

          
Adaptive VAr Control
  Automatically measures the size of the bank, and establishes VAr set points for maximum energy loss reduction.
Adaptive Voltage Guard
  Identifies voltage change from bank switching and inhibits Close operation if Voltage Guard plus present line voltage exceeds high voltage limit.
PhaseFind Function
  Locates current signal phase with respect to voltage phase and compensates for phase rotation and reversed wiring.
Reverse Power Functions
  Calculates proper Var setpoints to compensate for altered Var measurement in this condition.
Reverse Trip/Close Detection
  Automatically senses reverse wiring of the Close and Trip drive circuits which inhibits all switching (except manual).
Anti-hunt Function
  Automatically compensates for rapid bank tripping due to cycling loads or interaction from other switched banks on the feeder.
Undervoltage Inhibit
  Protects the capacitor bank switch from damage caused by low voltage.
      

Easy Programming
  Windows-based software allows programming for up
to 4 seasons, each with primary & override functions.
Multi-Function
  In addition to basic functions, override functions,
voltage bias, and reverse power control modes, additional functions such as real-time monitoring,
user programmable calendars, switching time delays/inhibits, and neutral current lockouts are provided.
Extensive Data Recording
  Recording capability includes a full spectrum of
user-defined load data & controller operations and
are easily uploaded via RS-232 or optional optical port.



Report Generation Capability
  Load data reports provide a spread sheet format file, graphing of load data, direct edit graph time period, Trip/Close status, and report printing and includes many editing features.
          
        
Specifications
                  
Ordering Information
Example
Model: 
45 1 1 N - C T S - D D A - SK 6 1 A
Section: 
1 2 3 4 - 5 6 7 - 8 9 10 - 11 12 13 14
Section 1 Basic Model Number
45 Autocap programmable capacitor with two-way communications
Section 2 Line Current Input (Current sensing device ordered separately
1 Fisher Pierce 1301 line post sensor (60A/V) or Lindsey sensor (100A/V)
2 CT (5A secondary)
0 None
Section 3 Neutral Current Sensor
1 Fisher Pierce AT929 sensor with 6 foot lead (supplied)
2 CT (not supplied)
3 VT (not supplied)
0 None
Section 4 Optical Communication Port
F Supplied
N None
Section 5 Counter/Display
C Electro-mechanical (counter 120 Vac only)
D 2-line display only (read only)
E Electromechanical counter and 2-line display (read only)
N None
Section 6 Temperature Sensor
T Supplied
N None
Section 7 Memory
S Standard 32K
E Expanded 128K
Section 8 Communications Protocol
F SmartSet (No comm. micro or flash memory)
D DNP 3.0 (comm. micro and flash memory installed)
         Note: For cellular phone or modem communication, select "F"
Section 9
& 10
Communications Options
BA Installed-Metrocom model 20043
BB Radio Ready
DA Installed-MDS model 9310, 9810
DB Radio Ready
NC Communications ready or radio upgrade
Note:
  • Installed=Radio installation by FP, supplied by customer. Communication micro, flash memory and power supply included.
  • Radio Ready= Radio installed by customer. Radio bracket, antenna mount and cables included. Communication micro, flash memory & power supply included.
  • Communications Ready (defined by selecting "D" in section 8)= Radio bracket an cables not included.
  • Power supply included. Comm. micro and memory installed.
  • Radio Upgrade (defined by selecting code "F" in section *)=Radio bracket and cables not included. Comm. micro and memory not installed (Controller board change out required for communications using a protocol other than SmartSet).
Section 11 External Wiring and Mounting Configuration
  Section 11 Four Jaw Meter Socket Mounting and Wiring
Section
11
1 2 3 4 5 6 External
ND Lug
Current
Inputs
FJ L N/GND TR CL - - NO NONE
GJ L N/COM TR CL - - YES NONE

Section 11 Six Jaw Meter Socket Mounting and Wiring
Section
11
1 2 3 4 5 6 External
GND Lug
Current
Inputs
SJ CSL N/GND L TR CSH CL NO LINE ONLY
TJ CSL N L TR CSH CL YES LINE ONLY
SM L N/GND CSL CSH TR CL NO LINE ONLY
TM L N CSL CSH TR CL YES LINE ONLY
SL L N/GND NSL NSH TR CL NO NEUTRAL ONLY
TL L N NSL NSH TR CL YES NEUTRAL ONLY
SK L N/GND/COM NSH CSH TR CL NO LINE+NEUT
TK L N/COM NSH CSH TR CL YES LINE+NEUT

Section 11 Bracket Mounting with Terminal Strip
Section
11
  External
GND Lug
Current
Inputs
BJ: POLE
WJ: WALL
WIRE TO TERMINAL STRIP AS SHOW BELOW YES NONE, LINE, NEUTRAL OR LINE+NEUTRAL

Terminal Strip (Aluminum Enclosure Only)

Socket for CT shorting switch available for SJ & TJ wiring

GND=System ground
N = Neutral
L = Line
RLY = Output relay armatures
CL = Close
TR = Trip
CSH = Line current signal High
CSL = Line current signal Low
NSH = Neutral current signal High
NSL = Neutral current signal Low

View looking
into socket

* Broken lines between terminals indicate removable jumper
Section 12 Enclosure Type
6 Luran
Section 13 Voltage/Frequency

1

120 Vac, 60 Hz
2 240 Vac, 60 Hz
3 120 Vac, 50 Hz
4 220 Vac, 50 Hz
5 240 Vac, 50 Hz