      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     
Powerflex Low Profile Capacitor Switching Controls Series 70A/80A

Powerflex Low Profile Capacitor Switching Controls Series 70A/80A The Fisher Pierce Powerflex™ Low Profile Capacitor Switching Controls Series 70A/80A are single function controls for VAr, Current, Voltage, or Temperature applications. Var controls use potential transformers and current input for reactive ampere sensing.The controls utilize bandwidth control to simplify settings and prevent errors.

The controls are packaged in a reinforced Lexan or aluminum enclosure. They can be mounted on a meter socket or bracket and are small and lightweight for easy installation.
          
Solid State Circuitry
  All sense and time circuitry is completely solid state.  
Input Protection  
  CT inputs are neutral and isolated from the line and is M.O.V. surge protected.
Indicating LED  
  Easy testing of trip and close set points.  
Standard Options  
  Close operations counter, auto-manual switch, fuse and test jacks are standards on all units.
Easy Installation  
  Small, lightweight enclosures can be mounted on a meter socket or a bracket.
         
   
Specifications
                         
Ordering Information
   Follow the model number examples as shown; then select from the tables below.
      (1) Basic Model
     (2) Time Delay
     (3) Mounting Style
     (4) Enclosure
     (5) Voltage/Frequency/Fuse
    

   
No. (1) Basic Model
2406 True RMS voltage, no bias
2412 True RMS voltage, bias by external contact
4620
4621
4608
4609
VAr (1301 Ser. input) grounded wye system
VAr (1301 Ser input) 3W-Delta
VAr (C.T. 12 Aac cont.) grounded wye system
VAr (CT 12 Aac cont.) ungrounded delta system
*4844
4846
4847
True RMS current (1301 Ser. Input)
True RMS current (CT)
True RMS current (AT929-10 Ser. Input)
5732
5734
Electronic temperature (70-120°F, close with increase)
Electronic temperature (0-50°F, close with decrease)
Code  (2) Time Delay

AA
AB

3-150 sec. adjustable, one range; Voltage, Current and VAr
3-300 sec. adjustable, two ranges; Voltage, Current and VAr

T 30-120 min.; Temp. only(with 60 sec. test position)
     (3) Mounting Style
S Six stab meter plug (Lexan or aluminum)
F Four stab meter plug (Lexan or aluminum)
W Flat wall bracket (aluminum only)
B Standard pole bracket (aluminum only)
     (4) Enclosure
7 Glass reinforced Lexan (6.5" x 8.6" x 3.1")
8 Aluminum (7.0" x 11.5" x 3.1")
      (5) Voltage/Frequency/Fuse
Input Fuse
3 240 Vac, 50 Hz 5A
5 120 Vac, 50 Hz 5A
6 120 Vac, 60 Hz 5A
8 120 Vac, 60 Hz 10A
  

Joslyn Hi-Voltage Royce Thompson Fisher Pierce

Home | About Us | Products | Library | Contact Us