Joslyn
vacuum switches are ideally suited for distribution sectionalizing applications.
They are virtually maintenance free, since they contain no oil or SF-6
gas and require inspection after only 15,000 operations. The switches
are supplied with mounting frames that can be easily mounted to poles
or other structures. The mounting frames can also integrate current and
voltage sensors, lightning arresters, and integral isolating switches. Joslyn vacuum switches are designed with fault closing ability and are not de-rated unlike SF-6 switches. Furthermore, the distribution sectionalizing switches can be applied up to 69kV, allowing use on sub-transmission systems. |
| Contains No Oil or SF-6 Gas | |
| Fault Closing Capability with no De-Rating | |
| Maintenance-Free, Long Life - 15,000 Operations | |
| Integrated, Low Current Motor Operator | |
| Manual Opening and Closing | |
| Distribution Vacuum Switches | ||||
|
Type
|
System
Voltage
(kV) |
Continuous
Current (A) |
Interrupting
Rating (A)2 |
Fault
Closing &
Momentary Current Rating (A)3 |
|
VSV
|
15
|
200
|
200
|
9000
|
|
VSV
|
25
|
200
|
200
|
9000
|
|
|
|
|
|
|
|
VBM
|
15
|
400
|
3000
|
20,000
|
|
VBM
|
15
|
600
|
4000
or 8000
|
20,000
|
|
VBM
|
251
|
400
|
3000
|
20,000
|
|
VBM
|
25
|
600
|
3000
|
20,000
|
|
VBM
|
34.51
|
600
|
600
|
20,000
|
| VBM | 34.5 | 300 or 600 | 3000 | 15,000 |
| VBM | 46 | 300 or 600 | 3000 | 15,000 |
| VBM | 694 | 300 | 3000 | 15,000 |
| Ratings Table References | ||
| 1 | Solidly Grounded System | |
| 2 | RMS Ampere Symmetrical | |
| 3 | RMS Ampere Asymmetrical | |
| 4 | Solenoid-Operated, 3-mechanisms | |
| Distribution Vacuum Switch Control Options |
| Automatic Sectionalizing Controls |
| Remote Supervisory Controls |
|