The
new TriModä 100 Series Vacuum Recloser raises
the standard of recloser performance by incorporating state-of the-art
vacuum interrupter technology with a long-life solenoid operated mechanism. The TriModä 100 is used in conjunction with PowerMAXä
micropocessor based controls. Joslyn Hi-Voltage has been a leader in solid dielectric insulation for over 35 years. The patented and field proven JOSLYTEä solid dielectric foam has been successfully used in other industry leading products such as the VerSaVacä and VarMasterä vacuum switches. |
| Long Operating Life | ||
| 10,000 maintenance-free operations. | ||
| Vacuum Interrupting | ||
| Advanced vacuum interrupter technology provides two duty cycle interruption life. | ||
| No Oil or Gas | ||
| Field-proven JOSLYTEä solid dielectric foam provides superior insulation and mechanical support around the vacuum interrupter and is environmentally friendly. | ||
| Long-Life Solenoid Operating Mechanism | ||
| Field-proven, self-lubricating design contains very few components thus increasing its reliability. | ||
| Highly Visible Mechanical Position Indicator | ||
| Large, reflective Open (Green) / Closed (Red) indicators are visible from ground level. | ||
| External, Easily Removable Current Transformers | ||
| Safety is ensured with the externally mounted current transformers (CTs) because they are surrounded with a grounded metal cover. The metal cover can easily by removed to access or replace the CTS | ||
| Manual Operation Handles | ||
The
yellow handle
permits mechanical opening and mechanically actuated, electrical closing
on the recloser. The non-reclosing lever provides the capability of blocking
reclosing after the first trip operation regardless of the number of recloses
preprogrammed in the control. |
||
| Specifications |
![]() |
Three controls integrated into one cabinet!
Features: |
| TriModä 100 Series Vacuum Recloser | ||||
|
Model
No. |
Voltage
Range
(kV) |
Continuous
Current (AMPS) |
Interrupting
Current
(kA RMS Symm.) |
Bil
(kV) |
|
115-6
|
4
- 17.1
|
630
or 800
|
6
|
110
|
|
115-10
|
4
- 17.1
|
630
or 800
|
10
|
110
|
|
115-12.5
|
4
- 17.1
|
630
or 800
|
12.5
|
110
|
|
127-6
|
17
- 29.3
|
630
or 800
|
6
|
125
|
|
127-10
|
17-
29.3
|
630
or 800
|
10
|
125
|
|
127-12.5
|
17-
29.3
|
630
or 800
|
12.5
|
125
|
| TriModä 100 Recloser Ratings | ||
| Description | 15kV | 27kV |
| Nominal System Voltage (kV, RMS) | 14.4 | 25 |
| Rated Maximum Voltage (kV, RMS) | 17.1 | 27 |
| Nominal Frequency (Hz) | 50 or 60 | 50 or 60 |
| Number of Phases | 1 | 1 |
| BIL (kV) | 110 | 125 |
| Power Frequency Withstand - Dry (kV) | 50 | 60 |
| Power Frequency Withstand - Wet (kV) | 45 | 50 |
| Continuous Current (A RMS) | 630 or 800 | 630 or 800 |
| 8-Hour Overload Current (A RMS) | 800 | 800 |
| Interrupting Current (kA RMS Symmetrical) | 6, 10 or 12.5 | 6, 10 or 12.5 |
| Making Current (kA Asym Peak) | 33 | 33 |
| Arc Extinction Medium | Vacuum | Vacuum |
| Insulating Medium | Solid
High Dielectric Foam |
Solid
High Dielectric Foam |
| Mechanical Operations | 10,000 | 10,000 |
| Ordering and Specifying Information | |||
| 1. | Select voltage class, continuous current, and interrupting current rating from the ratings table. | ||
| 2. | Select control & mounting configuration. | ||
| PowerMAXä 100 Direct Mount Remote - Pole Mount |
PowerMAXä 130 Remote - Pole Mount |
||
| 3. |
Specify cable length (Remote - Pole Mount only). |
||
| 4. |
Specify mounting frame. |
||
| 5. | Select options and accessories. | ||
![]() |
|
Home | About Us | Products | Library | Contact Us | Chinese Site Joslyn Hi-Voltage - 4000 E 116th Street, Cleveland, Ohio 44105 USA Email: T&B Contact InformationCopyright © 2001 Joslyn Hi-Voltage. All rights reserved. |