| Distribution Vacuum Switches | |||
|
System
Voltage
(kV) |
Continuous
Current (A) |
Interrupting
Rating (A)2 |
Fault
Closing &
Momentary Current Rating (A)3 |
|
15
|
400
|
3000
|
20,000
|
|
15
|
600
|
4000
or 8000
|
20,000
|
|
251
|
400
|
3000
|
20,000
|
|
25
|
600
|
3000
|
20,000
|
|
34.51
|
600
|
600
|
20,000
|
| 34.5 | 300 or 600 | 3000 | 15,000 |
| 46 | 300 or 600 | 3000 | 15,000 |
| 694 | 300 | 3000 | 15,000 |
| Ratings Table References | ||
| 1 | Solidly Grounded System | |
| 2 | RMS Ampere Symmetrical | |
| 3 | RMS Ampere Asymmetrical | |
| 4 | Solenoid-Operated, 3-mechanisms | |
| Ordering Information | ||
|
TWO
SWITCHES & CONTROLS ARE NEEDED FOR A PREFERRED ALTERNATE SYSTEM
|
||
| 1 | Select VBM switch from ratings table above. | |
| 2 | Selecting mounting frame (standard wood pole mounting frame, frame with current sensor mounting provisions, frame with integral isolating switches). | |
| 3 | Select Automatic Sectionalizing Voltage-Time Control and options. | |
| 4 | Specify cable length between VBM switch and control. | |
| 5 | Specify distance between controls. | |
|
Example:
|
||
| 1 | Two 15kV, 600A, motor operated VBMs. | |
| 2 | Standard wood pole mounting frames. | |
| 3 | Two automatic sectionalizing controls with high current board, 3 phase voltage sensing board, cable connector on bottom of control cabinet. | |
| 4 | 35 ft. shielded control cable with connectors on both ends. | |
| 5 | 200 ft. between controls. | |
|
Home | About Us | Products | Library | Contact Us | Chinese Site Joslyn Hi-Voltage - 4000 E 116th Street, Cleveland, Ohio 44105 USA Email: T&B Contact InformationCopyright © 2001 Joslyn Hi-Voltage. All rights reserved. |