Joslyn reclosing
sectionalizers are unique in combining recloser and sectionalizer logic
without current coordination problems. |
| * Indicates feature is DIP switch selectable |
| Safety Feature * | |
| Maintenance safety feature automatically opens the switch with no reclose if voltage is lost while control is set in the manual position which prevents reclosing into personnel on the line. | |
| "Selected Close" Feature* | |
| Allows selective closing to energize a distribution line segment from a selected source. | |
| Proprietary "Immediate Second Close" Feature* | |
| Significantly reduces total system restoration time. | |
| Voltage Time "(V-T) Close Inhibit" Feature* | |
| Automatically prevents closing if line is energized on both sides of a "V-T" switch, while it is in the open position. |
| Power On-Off Switches and Indication | |
| Remote Indication Contacts | |
| Settings Easily Visible | |
| Timer and option setting label to record all setting on inside of front door. | |
| Control Check | |
| All controls are "burned in" for a minimum of 48 hours at 140 degrees Fahrenheit with full control power to detect components infant mortality. | |
| Tested to Standard | |
| Control has been tested to pass the ANSI/IEEE C37.90.1, 1974 standard. | |
| Manual Operation | |
| Open and close toggle switch. | |
| No Batteries Required | |
| Microprocessor Controlled | |
| On board ROM (EPROM) and RAM. | |
| Open-Tie (O-T) Option* | |
| "Source Side Lockout Logic" Timer* | |
| With customer settable source side lockout timer and (O-T) source side reset timer. |
| Ordering Information | ||||||||||
| 1 | Specify version | |||||||||
|
||||||||||
|
Options
and Accessories
|
|
| Three-Phase Voltage Sensing Option P.C. Board. (6 inputs maximum) | |
| Remote Control Input Option P.C. Board | |
| High Overcurrent with Voltage Loss Options P.C. Board. (includes 3 optional responses) | |
| "OT" Option Relays. (For upgrading a version 4 to a version 3) | |
| Terminal Box - mounted on Vacuum Switch for hard wiring between Switch and Control | |
| Shielded Cable with Plug on both Cable ends and Cable Connector on the bottom of the Control Cabinet | |
| Cable Connector on the bottom of the Control Cabinet and Plug with Cable for 120 VAC Power Source, 25 foot length standard | |
| External Lamp (Amber) Lockout Indication | |
| External Lamp (Red/Green) for Vacuum Switch (Closed/Open) Indication respectively | |
| Simulator Control Box with Cable - Tester Box for Switch Simulation | |
| Low Temperature Package for Operation to -50C | |
| Control Cabinet Door Closing Toggle Clamps | |
| Cable Connector on the bottom of the Control Cabinet and plugs with Cables for three (3) phase 120 VAC inputs. Specify length | |
| Operations Counter in the Control. (Note that a mechanically actuated Operations Counter is supplied on the VBM Switch as standard) | |
| Control Cabinet with Extra Space for a RTU, and/or RADIO | |
| Control Cabinet with Battery Backup for Dead Line Switching | |
| Joslyn Control with Power Supply and Battery Backup for Radio and RTU. Specify RTU and Radio | |
| High Security Cable with Internal Connectors | |
|