The Smartlinkä Series 5000 provides reliable and cost effective 2-way communications for automated fault reporting from Fisher Pierce Series 1548 radio FCIs. The unit provides flexible reporting of permanent and temporary (optional) fault conditions. The Series 5000 uses technology from Telemetric to communicate over digital or analog cellular data networks. The secure web-based application displays the device data which can be queried or polled remotely. A variety of user specified fault alarms can be configured to notify a designated person of a reported event by email, pager, or text message. The unit will immediately report alarm conditions including: permanent fault on any phase, phase status, fault cleared with status by phase, over- or under-voltage set points on control power phase, and low battery alarm.
|
| Specifications | ||
| Electrical/Environment | ||
| Operating voltage: 95-135 Vac, 60Hz | ||
| Surge Withstand: ANSI/IEEE C37.90.1-2002, 4kV min. @ 1.2/50 μs surge | ||
| FNM style Slo-Blo fuse, barrel mounted | ||
| Operating temperature range: -40 deg C to +70 deg C | ||
| Fault Indicator Receiver | ||
| Operating Frequency: 312 MHz | ||
| Receiver Range: 100’ minimum typical | ||
| Receiver Sensitivity Adjustment: Selectable via local configuration or web application to max range of local RF radio (low gain, high gain) | ||
| Certification: Complies with FCC part 15 emissions | ||
| Cellular Radio Technology | ||
| Dual-band, dual-mode supporting GSM/GPRS 850/1900 MHz | ||
| Nationwide GPRS support via Cingular Wireless and affiliated roaming partners with a variety of application data plans. | ||
| Transmit power: 0.6 to 3W | ||
| External mounted antenna, flexible dual-band (850/1900) cellular, SMA(F) connector | ||
| Fault receiver antenna (312MHz RF system, BNC connector) | ||
| Battery Backup | ||
| Standard: Lead Acid, rechargeable 12V (3 to 5 years expected service life) | ||
| Carryover time: 4-hour typical, 3-hour minimum | ||
| Recharge time after 3-4 hour carryover: 6 hrs typ. | ||
| Accessibility: Front panel replaceable | ||
| Status message sent weekly or by request | ||
| Enclosure | ||
| Lexan enclosure for meter socket mounting | ||
| NEMA 3R Rating | ||
| Security latch for meter seal or 3/8” hasp padlock |
| Digital Outputs to the 4400 control | ||
| 1 | Change Mode Switch Bank Reset Daily Close Count |
Remote/Local Close/Trip Clear Neutral Current Lockout |
| *Manual toggle switch on 4400 control disables all automatic and remote control functions | ||
| Digital Inputs to the 4400 control | ||
| 1 | Close Inhibit Trip Inhibit Neutral Current Status VT Wire Neutral Current Protection Anti-Hunt Last Switch Opn. Command |
Inhibit/Clear Inhibit/Clear Lockout/Clear Line-Neut/Line-Line Enabled/Disabled Enabled/Disabled Trip/Close |
| Analog Inputs from the 4400 control | ||
| 1 | - Voltage, secondary (V) - Last Delta E (V) - Current, primary (A) - Power, 3PH (kW) - VAr, 3PH (kVAr) - Power Factor (through web access) - Neutral Current (A) - Temperature deg F - Total Close Count - Close Today Count - Capacitor Control Run time (hrs) - Maximum Close Count per Day Setpoint - Operation Mode - PCC Identification Number |
- Neutral Current Sensor Type - Current Sensor Phase - Voltage Transformer Ratio - Phase Rotation - Current Direction (Forward/Reverse) - Current Transformer Ratio - Current Sensor Type - Total Angle Correction (deg) - Reverse Power Control Action - Season # - Primary Control Function - Close Setpoint - Trip Setpoint |
|