      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     

   
                                        
Adaptive Trip Faulted Circuit Indicators - Series 1547
Operating Speed:

Coordinates with properly applied current limiting fuses, provided that the FCI trip-set and the trip-release conditions are satisfied.

Fault Withstand Capability: 25 kA for 10 cycles per ANSI/IEEE 495-1986
Operating Current Range: The FCI will operate from minimum reset current to 800 amperes for trip operation. The maximum continuous current rating for the FCI is 800 amperes.

Reset Function:

Resets to normal indication according to unit selected from Ordering Information, Table 3 (Relay Delay).

Reset Current Level:  
1 5/8" sensor with U-lamination: 1.0A
2 3/16 " sensor with U-lamination: 1.5A
1 5/8" sensor with U-lamination: 2.0A
2 3/16" sensor with U-lamination: 3.0A
Operating Temperature :  
Sensor: -50° C to + 90° C
Indicator: -40° C to + 85° C
Submergibility: Tested to 30 feet.
Life Expectancy: (1547A Series Flag-type) 20 + years.
Rated Battery Life: 800 hours of operation.
Lithium cell, rated for 10 year life.
(1547B Series LED-type; 1547C Series fiber optic type)
Line Current: The FCI adjusts to line current 40 - 60 seconds after the line current exceeds minimum reset current.
Trip Operation:

A) Trip Enable Condition: Occurs whenever line current increases by the rate of 100 amperes (or greater) within 3 cycles

B) The FCI will indicate trip only when the line current drops 1/2 amperes above the minimum reset current within 40-60 seconds after the trip-set condition occurs.

Approx. Shipping Weight:

2.0 lbs
  

Joslyn Hi-Voltage Royce Thompson Fisher Pierce