Thomas & Betts
Press Room
Sales Partner Login
      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     

   
                                        
Current-Reset Fault Indicators Series 1514/15
Trip Current: Factory preset from 50 to 1500A.
Trip Current Accuracy: ±10%
Trip Response Speed: Coordinates with properly applied current-limiting or expulsion fuses.
Reset Current: Factory preset for 1.2, 1.5, 3.0, and 5.0A.
Fault Withstand Capability: 25kA for 10 cycles per ANSI/IEEE 495-1986.
Maximum Continuous Load Current: 1000A
Operating Temperature:
-40°C to +85°C

Submersibility:

Tested to 30 feet. Exceeds ANSI/IEEE 495-1986.

Life Expectancy:

30+ years (flag type)
Rated Battery Life:
10 years (long life lithium cell)
 
Model 1514B/1515B: 
Model 1514D:
 
800 hours of operation
300 hours of operation

Warranty:

3 years

Approx. Shipping Weight:

 
 
Series 1514, single phase: 
Series 1515, three phase:

2.0 lbs.
4.9 lbs.
  

Joslyn Hi-Voltage Royce Thompson Fisher Pierce