Thomas & Betts
Press Room
Sales Partner Login
      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     

   
                                        
Overcurrent Trip, Automatic Time Reset Fault Indicators Series 1541/42/43
Fault Registration: Red, high intensity light emitting diode (LED) with choice of hard wired of fiber optic cable remote mounting or audible intermittent beeper signal.
Trip Current: Factory preset to customer specifications.
Range 50A and 100A to 1500A in 100A increments.
Trip Current Accuracy: ±10% of trip rating (calibrated using 1" diameter cable for 400A trip or less; or 2.0" diameter cable for greater than 400A trip.)
Trip Response Speed: Consult trip curves. Coordinated to properly applied link, expulsion, power and current limiting fuses.
Reset Time: 4 hours, 2 hours, 1 hour.
Manual trip/reset standard.
Overload Capacity : Capable of withstanding 25,000A for 10 cycles.
Continuous Load Current: Rated at 1000A (maximum)
Temperature Range:
-40°C to +85°C

Submersibility:

Tested to 30 feet.

Operating Battery Life:

800 hours for LED indication
160 hours for audible indication
Both with 10 year life at 20
°C.
Battery:
Long life lithium cell

Cable Ranges:

0.63 to 1.58"; 1.58 to 2.36"; 2.36 to 3.55"

Remote Fiber Optic Options:

Permanent or removable
(standard 10 feet with a maximum of 30 feet)
  

Joslyn Hi-Voltage Royce Thompson Fisher Pierce

Home | About Us | Products | Library | Contact Us

Joslyn Hi-Voltage - 4000 E 116th Street, Cleveland, Ohio 44105 USA   Email: jhv_info@tnb.com
Copyright © 2001 Joslyn Hi-Voltage. All rights reserved.
   
Royce Thompson