      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     

   
                                        
AutoCap Series 4400 Controller
Voltage Range
PCC Power & True RMS Sensing
95-140 V, 60 Hz
190-280 V, 60 Hz
95-125 V, 50 Hz
190-50 V, 60 Hz
Sensing Accuracy:
± 0.5% of reading over temperature.
Voltage Control and Override:
95-140 V / 190-280 V secondary in 0.1 V increments.
Voltage Transformer Ration (VTR):
1:1 to 1000:1 in 0.1:1 increments.
Current
Sensors:
  • Fisher Pierce series 1301 line post sensor
    (60 A/V) ... 4-800A true rms.
  • Lindsey line post sensor (100 A/V) ...4-800A true rms.
  • CT secondary ... 0.1-20A true rm.
Accuracy: ± 1.0% Reading, ± 0.2% Range, ± sensor error.
Angle Accuracy: ± 1 deg., ± sensor error.
Current Control - Range/Resolution:
Line post sensor ... 4-800A in 0.1 A increments.
Current Transformer ... 0.1-2.0A secondary in 0.01A increments
Current Transformer Ratio (CTR):
5:5 to 2000:5 in 1:5 increments.
VAr Control - Range/Resolution
Adaptive VAr: Limited only by secondary voltage range x current sensing range.
3ø kVAr: Range ± 1 to 99,999 kVAr in 1 kVAr increments.
Time Control - Range/Resolution:
Two Close and two Trip settings for each day of the week in 24:00 hour clock, in 1 minute increments.
Temperature Control - Range/Resolution
Sensor: Located on bottom of enclosure with radiation shield.
Range: -40° to +122°F (-40° to +50°C) outside air ambient.
Accuracy: ± 2°F/1°C
Temperature Control, Override,
and Bias:
  • Close on High temperature.
  • Close on Low temperature.
  • Range ... -40° to +122°F (-40° to +50°C) outside air ambient in 1°F (1°C) increments.
Serial Communications Port: DB9 female connector
Optical Communications Port: Type 2
Operating Humidity Range: 0-95% non-condensing.
Surge Withstand: ANSI C62.41-1987
Electrostatic Discharge Test: 15kV applied to all accessible parts, IEC 801-2.
Output Relay Rating: 10A continuous. 50A, 50% PF, 6 cycles make only.
Relay Type: Momentary (two relays).
Contact closure period: 1-1000 sec. in 1 sec. increments.
2A controller fuse.
Enclosures:  
Six Stab Lexan: 8.5h x 6.5w x 4.0d in. Includes optical port and electromechanical operations counter options.
Aluminum: 11.5 x 7.0w x 4.0d in. Includes optical port and electromechanical counter options.
Computer Requirements: SmartSet setup software requires Windows 3.1 or better.
Series 1301 Line Post Sensor
Calibration Accuracy at 120A: ± 1%
Linearity Error: 3-1200A, ± 0.5°
Temperature Error: ± 0.02%/°C
7th Harmonic Response: 82%
See Fisher Pierce Series 1301 bulletin FP054 for complete specifications.
  