      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     

   
                                        
AutoCap Series 4500 Controller & Recorder With Two-Way Communications
Radio
Maximum Radio Dimensions:
13.5"h x 7.25' x 2.25"d
Radio Power Supply:
13 Vdc, 2.0A continuous, 3.0A transmit
Electrical
Operating Voltage Ranges: 95-140 V, 60 Hz
190-280 V, 60 Hz
95-125 V, 50 Hz
190-250 V, 50 Hz
 
Surge Withstand:
ANSI C62.41-1987
Electrostatic Discharge Test: 15kV applied to all accessible parts, IEC 801-2.
Output Relay
Number: Two
Type: Momentary closure
Maximum Continuous Load: 10A
Maximum Inrush: 50A, 50% PF, 6 cycles, make only
Contact Closure Period: Programmable 1 - 1000 seconds, in 1 sec. increments
Fuse Rating
Output to Capacitor Switch: 10A FNM Slo-Blo® load fuse.
Controller Input: 2A controller fuse.
RS 232 Communications Port: db9 female connector
Optical Communications Port: Type 2
Mechanical
Enclosure:
Luran, NEMA 3R
Mounting:
4 or 6 jaw meter base, wall or pole bracket
Dimensions: 15.25"h x 9.25"w x 8.50"d
Environmental
Operating Temperature: -40C to 80C (-40CF to +176F)
Humidity Range: 0 to 95% (non-condensing)
Measurement Performance
Voltage Secondary Resolution: 0.1 Vac
Accuracy: ± 0.5% of reading over temperature.
Range: Same as operating range, true rms
Primary VT Ratio Range: 1:1 to 1000:1 in 0.1:1 increments
Current
Resolution: Fisher Pierce 1301 sensor: 0.1A
Lindsey line post sensor: 0.1A
Current transformer: 0.01A (secondary)
Accuracy: ± 1.0% Reading, ± 0.2 Range, ± sensor error.
Range: Fisher Pierece 1301 sensor ...4-800A true rms
Lindsey line post sensor: 4-800A true rms.
Current transformer: 0.1-20A (secondary) true rms
Current Transformer Ratio (CTR): 5:5 to 2000:5 in 1:5 increments.
Reactive Power (VAr)
Resolution: 1 kVAr
Range: ± 99,999k VAr
Time Clock
Resolution: 1 second
Accuracy: ± 10 minutes per year
Range: 24 hour clock
Settings: 1 minute increments
Phase Angle
Resolution: 0.1°
Accuracy: ± 1°
Range: 0° - 359°
Neutral Current
Resolution: Fisher Pierce AT929 sensor:0.1A
Current Transformer: 0.01A (secondary)
Accuracy: ± 1% of reading, ± 0.2% range, ± sensor error
Range: Fisher Pierce AT929-400 sensor: 1 to 60A
Current Transformer Ratio: 5 to 2000:5
Voltage Transformer: 0-120V(secondary)
Controller Processor
Memory Size: 32 kB (standard), 128 kb (option)
Memory Types: EPROM, NVRAM and battery backed RAM
Series 1301 Line Post Sensor
Calibration Accuracy at 120A: ± 1%
Linearity Error: 3-1200A, ± 0.5°
Temperature Error: ± 0.02%/°C
7th Harmonic Response: 82%
*See Fisher Pierce Series 1301 bulletin FP054 for complete specifications.
  