      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     

   
                                        
PowerflexÒ Low Profile Capacitor Switching Controls
Input Voltages (All Models):
105 to 135 Vac, 50/60 Hz (VAr, 60 Hz only)
200 to 260 Vac, 50 Hz (except VAr)

Sensing Signals:

Voltage-2400 Series
105 to 135 and 200 to 260 Vac, 50/60 Hz.

VAr-4620, 4621 Series
High Accuracy 1301 Series Sensor

VAr-4608, 4609 Series
5 Aac C.T.secondary

Current-4844 Series
1301 Series Sensor

Current-4846 Series
5 Aac CT secondary

Temperature-5732 & 5734 Series
Fisher Pierce Temperature Sensor

Operating Ranges and Accuracy:

Voltage-2406 Series
Cap On: 105 to 130 Vac ± 1 Vac, 7X and 8X Series
200 to 260 Vac ± 2 Vac, 73 Series

Cap Off Bandwidth: 1 to 10 ± 0.5 Vac. (120V input).
2 to 20 ± 1.0 Vac. (240V input).

Voltage-2412 Series
Cap On: 105 to 130 Vac, 7X and 8X Series
200 to 260 Vac ± 2 Vac, 73 Series

Cap Off Bandwidth: 1 to 10 ± 0.5 Vac (120 V input)
2 to 20 ± 0.5 Vac (240V input).
Bias: 1 to 10 ± 0.5 Vac (120 V input)
2 to 20 ± 1.0 Vac (120 V input)
Bias Actuation: 2412-external contact closure.

Current-4844 Series (1301 Series Sensor)
Cap On Ranges: 1 to 30, 5 to 150, 20 to 600,
60 to 1800 Aac ± 5% of setting ± 2 % of range.
Cap Off Bandwidth: 60 to 100% ± 2% of setting.

Current 4846 Series (CT 12 Aac max.)
Cap On Ranges: 0.1 to 3, 0.4 to 12 Aac,
Cap Off Bandwidth: 60 to 100% ± 2% of setting.

Current 4847 Series (AT929-10 Sensor))
*Cap On Ranges: 1 to 3, 5 to 150, 20 to 600 Aac,
± 5% of setting ± 2% of range.
Cap Off Bandwidth: 60 to 100% ± 2% of setting.

VAr-4620 Series (High accuracy-1301-Wye system).
4621 Series (High accuracy-1301-Delta system).
Cap On Ranges: Ar ± 3% full scale/max. line current:
0 to 30/200, 0 to 120/800, 0 to 300/200.
Cap Off Ranges less lagging than Cap On:
0 to 45, 0 to 180, 0 to 450 AR ± 2% of setting.

VAr-4608 Series (CT 12 Aac max.-Wye System)
4609 Series (CT 12 Aac max.-Delta System)

Cap On Ranges: AR ± 3% full scale/max. secondary CT
Current: 0 to 0.3/3, 0 to 1.2/12.

Cap Off Ranges less lagging than Cap On:
0 to 0.45, 0 to 1.8 AR ± 2% of setting.

Temperature-5732 Series
(Close with increasing temperature.)
Cap On Range: 70 to 120°F ± 3°
Cap Off Range: 2 to 20°F ± 2°.

Temperature-5734 Series
(Close with increasing temperature.)
Cap On Range: 70 to 50°F ± 3°
Cap Off Range: 2 to 20°F ± 2°.

Output Contractor:
10 Aac continuous at 120/240 Vac.
50 Aac, 50% PF, 125 Vac,
6 cycles make only.
Load Fuse:
FNM5 slo-blo., 5 Amperes (73, 75, 76 and 86 Series)
FNM10 slo-blo., 10 Amperes (78 and 88 Series)
Operating Temperature: -30°C to +60°C
Time Delay Ranges:
Voltage, Current and VAr
3-150 seconds, single range.
3-150 and 150-300 dual range.
± 5% of range ± 5% setting.

Time Switch
Not Applicable.

Temperature
30-120 minutes (60 second test position).