| PowerflexÒ Current Sensor Series 1301 | |||
| Model 1301-17A |
Model 1301-47A |
Model 1301-27A |
|
| Nominal 3-phase rating, kV: | 15 | 25 | 35 |
| Maximum operating voltage to ground, kV: | 9.5 | 15 | 22 |
| 60 Hz dry flashover, kV: | 80 | 95 | 110 |
| 60 Hz wet flashover, kV: | 55 | 60 | 85 |
| Impulse flashover, positive kV: | 105 | 140 | 180 |
| Impulse flashover, negative kV: | 130 | 175 | 205 |
| Impulse withstand kV: | 95 | 130 | 160 |
| Radio influence test voltage, kV | 10 | 15 | 22 |
| Radio influence voltage at 1 mHz, microvolts, kV | 110 | 500 | 500 |
| Dry arcing distance, inches | 6.5 | 9.5 | 11.5 |
| Leakage distance, inches | 11 | 17 | 25 |
| Weight, pounds | 13 | 19 | 28 |
| Cantilever strength, pounds | 2000 | 1700 | 1500 |
|
Home | About Us | Products | Library | Contact Us Joslyn Hi-Voltage - 4000 E 116th Street, Cleveland, Ohio 44105 USA Email: jhv_info@tnb.comCopyright © 2001 Joslyn Hi-Voltage. All rights reserved. |