| TriMod 300 Three Phase Vacuum Recloser | |
| Scope: |
This Specification contains the requirements for the design and manufacture of three-phase vacuum interrupting circuit reclosers. |
| Reference Standards: | The recloser shall be designed, tested and manufactured in accordance with ANSI C37.60 for automatic circuit reclosers, including other applicable ANSI, NEMA, IEEE standards as defined in the reference section of the standard. |
| Service Conditions: | Service conditions for the recloser shall be usual standards for installation; ambient temperatures from -30°C to +40°C at altitudes below 1000M. For altitudes above 1000M, Table 1 of ANSI C37.60 shall define the altitude correction factor to be used. Unusual service conditions, such as temperature extremes, will be specified. |
|
Switch Construction: |
The recloser shall
be suitable for outdoor applications. The recloser tank shall be totally
enclosed with corrosion resistant cast aluminum. A pressure equalizing
system to prohibit ingress of moisture into the switch shall be used.
No heaters shall be used within the recloser. The current transformer shall be externally surrounded by a grounded metal surface to limit the possibility of hazardous voltage entering the control compartment, via the current transformer circuits, in the even of an external high voltage flashover. Switch position indication for each phase shall be located on the bottom
of the recloser to permit viewing from the ground. |
| Recloser Performance Requirements: | The recloser shall be rated for a minimum mechanical life of 10,000 open and close operations without any maintenance.
The vacuum interrupter contacts shall be rated for a minimum of 2 duty cycles as defined by ANSI C37.60. The recloser shall be provided with a hot-stick operable manual tripping lever that requires no external power for operation. |
|
Home | About Us | Products | Library | Contact Us Joslyn Hi-Voltage - 4000 E 116th Street, Cleveland, Ohio 44105 USA Email: jhv_info@tnb.comCopyright © 2001 Joslyn Hi-Voltage. All rights reserved. |