| Voltage-Reset Fault Indicators Series 1516 | |
| Trip Current: | Factory preset from 100 to 1500A. |
| Trip Current Accuracy: | ±10% |
| Trip Response Speed: | Coordinates with properly applied current-limiting. |
| Reset Voltage (factory preset): | |
|
120V
rating:
277V rating: |
minimum
reset voltage: 102V minimum reset voltage: 235V |
| Maximum Reset Response Time: | 60 seconds |
| Reset Lead Length: | 4 or 6 feet. |
| Fault
Withstand Capability: |
25kA for 10 cycles per ANSI/IEEE 495-1986. |
|
Secondary Voltage Surge Withstand Capability: |
Conforms to ANSI/IEEE C62.41. |
|
Maximum Continuous Load Current: |
1000A |
| Operating
Temperature: |
10 years (long life lithium cell) |
|
Sensor: Indicator: |
-50°C to +90°C -40°C to +85°C |
|
Submersibility: |
Tested to 20 feet. |
|
Life Expectancy: |
20+ years. |
|