      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
     

   
                                        
Voltage-Reset Fault Indicators Series 1516
Trip Current: Factory preset from 100 to 1500A.
Trip Current Accuracy: ±10%
Trip Response Speed: Coordinates with properly applied current-limiting.
Reset Voltage (factory preset):  
120V rating:
277V rating:
minimum reset voltage: 102V
minimum reset voltage: 235V
Maximum Reset Response Time: 60 seconds
Reset Lead Length: 4 or 6 feet.
Fault Withstand Capability:
25kA for 10 cycles per ANSI/IEEE 495-1986.

Secondary Voltage Surge Withstand Capability:

Conforms to ANSI/IEEE C62.41.

Maximum Continuous Load Current:

1000A
Operating Temperature:
10 years (long life lithium cell)
 
Sensor: 
Indicator:
 
-50
°C to +90°C
-40
°C to +85°C

Submersibility:

Tested to 20 feet.

Life Expectancy:

20+ years.
  